Summary

  • define when smoke-exhaust review should use Room height versus modeled Ceiling elements
  • require review and Excel export to use the same ceiling-height source
  • document the project-confirmed opening ratios: projected/top-hung 1.0, casement 0.5, horizontal sliding 0.5, fixed 0
  • keep unknown windows visibly flagged even when temporarily assumed as projected
  • standardize the formal name 橫拉窗 (Horizontal Sliding Window)

Validation

  • repository QA/QC: 61 PASS, 0 FAIL
  • upstream contribution scope: only domain/smoke-exhaust-review.md