Example for the exergy analysis in TESPy. Find more information about the exergy analysis feature in the respective online documentation.
The so called "Solar Energy Generating System (SEGS)" model has the following topology:
Clone the repository and install dependencies. We recommend using uv:
uv syncto create a virtual environment and install all dependencies. Then run the model script with
uv run SEGS.pyAlternatively, using pip:
pip install .The model is implemented as a subclass of TESPy's ModelTemplate in
SEGS.py. Use the Jupyter notebook SEGS.ipynb for interactive use of
the model, cycle diagrams, validation and exergy analysis results.
uv run --with jupyter jupyter lab SEGS.ipynbOn top of the python script, an EBSILON model (v14.03.01) for the identical setup is provided for validation. The results are available in the respective flowsheet. The solar field is not considered for further investigation, thus it represents a heat input only.
The original data of the plant are partially obtained from the following reports:
F. Lippke, Simulation of the part-load behavior of a 30 MWe SEGS plant, Technical Report SAND-95-1293, Sandia National Lab., Albuquerque, 1995. URL:https://www.osti.gov/biblio/95571. doi:10.2172/95571.
D. Kearney, C. E. Miller, Technical Evaluation of Project Feasibilty for SEGS VI, Technical Report,1988. Submitted to Luz Solar Partners VI.
The TESPy model is validated against the EBSILON model:
| parameter | TESPy | EBSILON | δ in % |
|---|---|---|---|
| grid power in MW | 31.769 | 31.769 | -0 |
| HTF return temperature in °C | 296.254 | 296.254 | -0 |
| Connection | e_PH in kJ/kg | e_T in kJ/kg | e_M in kJ/kg | E_PH in MW | E_T in MW | E_M in MW |
|---|---|---|---|---|---|---|
| 1 | 1197.3 | 1187.4 | 9.9 | 46.66 | 46.27 | 0.39 |
| 2 | 1197.3 | 1187.4 | 9.9 | 46.66 | 46.27 | 0.39 |
| 3 | 977.5 | 974.2 | 3.3 | 38.09 | 37.96 | 0.13 |
| 4 | 977.5 | 974.2 | 3.3 | 35.20 | 35.08 | 0.12 |
| 5 | 869.2 | 867.5 | 1.8 | 31.30 | 31.24 | 0.06 |
| 6 | 869.2 | 867.5 | 1.8 | 29.14 | 29.08 | 0.06 |
| 7 | 1074.3 | 1072.7 | 1.6 | 36.01 | 35.96 | 0.05 |
| 8 | 884.5 | 883.8 | 0.7 | 29.65 | 29.63 | 0.02 |
| 9 | 884.5 | 883.8 | 0.7 | 27.46 | 27.43 | 0.02 |
| 10 | 653.7 | 653.6 | 0.2 | 20.29 | 20.29 | 0.01 |
| 11 | 653.7 | 653.6 | 0.2 | 19.14 | 19.13 | 0.01 |
| 12 | 469.8 | 469.8 | -0.0 | 13.75 | 13.75 | -0.00 |
| 13 | 469.8 | 469.8 | -0.0 | 13.00 | 13.00 | -0.00 |
| 14 | 287.9 | 287.9 | -0.1 | 7.97 | 7.97 | -0.00 |
| 15 | 287.9 | 287.9 | -0.1 | 7.65 | 7.65 | -0.00 |
| 16 | 115.8 | 115.9 | -0.1 | 3.08 | 3.08 | -0.00 |
| 17 | 99.7 | 99.8 | -0.1 | 3.10 | 3.10 | -0.00 |
| 18 | 1.7 | 1.8 | -0.1 | 0.05 | 0.06 | -0.00 |
| 19 | 3.3 | 1.9 | 1.4 | 0.10 | 0.06 | 0.04 |
| 20 | 3.8 | 2.5 | 1.4 | 0.12 | 0.08 | 0.04 |
| 21 | 10.4 | 9.5 | 0.9 | 0.32 | 0.29 | 0.03 |
| 22 | 11.7 | 10.8 | 0.9 | 0.36 | 0.34 | 0.03 |
| 23 | 29.4 | 28.6 | 0.8 | 0.91 | 0.89 | 0.02 |
| 24 | 30.6 | 29.9 | 0.8 | 0.95 | 0.93 | 0.02 |
| 25 | 59.0 | 58.3 | 0.7 | 1.83 | 1.81 | 0.02 |
| 26 | 115.4 | 114.7 | 0.7 | 4.50 | 4.47 | 0.03 |
| 27 | 130.2 | 117.8 | 12.4 | 5.07 | 4.59 | 0.48 |
| 28 | 135.6 | 123.2 | 12.4 | 5.28 | 4.80 | 0.48 |
| 29 | 176.6 | 165.5 | 11.1 | 6.88 | 6.45 | 0.43 |
| 30 | 180.1 | 169.0 | 11.1 | 7.02 | 6.59 | 0.43 |
| 31 | 232.6 | 222.3 | 10.3 | 9.06 | 8.66 | 0.40 |
| 32 | 412.0 | 401.8 | 10.2 | 16.06 | 15.66 | 0.40 |
| 33 | 418.1 | 407.9 | 10.2 | 32.90 | 32.09 | 0.81 |
| 34 | 736.9 | 726.6 | 10.2 | 57.98 | 57.17 | 0.81 |
| 35 | 1055.6 | 1045.4 | 10.2 | 41.14 | 40.74 | 0.40 |
| 36 | 977.5 | 974.2 | 3.3 | 2.89 | 2.88 | 0.01 |
| 37 | 237.0 | 233.7 | 3.3 | 0.70 | 0.69 | 0.01 |
| 38 | 187.0 | 183.8 | 3.3 | 0.55 | 0.54 | 0.01 |
| 39 | 185.9 | 184.1 | 1.8 | 0.55 | 0.54 | 0.01 |
| 40 | 869.2 | 867.5 | 1.8 | 2.16 | 2.16 | 0.00 |
| 41 | 498.2 | 496.4 | 1.8 | 2.71 | 2.70 | 0.01 |
| 42 | 177.0 | 175.2 | 1.8 | 0.96 | 0.95 | 0.01 |
| 43 | 135.3 | 133.5 | 1.8 | 0.74 | 0.73 | 0.01 |
| 44 | 133.9 | 133.2 | 0.7 | 0.73 | 0.73 | 0.00 |
| 45 | 884.5 | 883.8 | 0.7 | 2.20 | 2.19 | 0.00 |
| 46 | 653.7 | 653.6 | 0.2 | 1.16 | 1.16 | 0.00 |
| 47 | 63.9 | 63.8 | 0.2 | 0.11 | 0.11 | 0.00 |
| 48 | 37.1 | 37.0 | 0.2 | 0.07 | 0.07 | 0.00 |
| 49 | 36.9 | 36.9 | -0.0 | 0.07 | 0.07 | -0.00 |
| 50 | 469.8 | 469.8 | -0.0 | 0.75 | 0.75 | -0.00 |
| 51 | 242.3 | 242.3 | -0.0 | 0.82 | 0.82 | -0.00 |
| 52 | 32.7 | 32.7 | -0.0 | 0.11 | 0.11 | -0.00 |
| 53 | 14.8 | 14.8 | -0.0 | 0.05 | 0.05 | -0.00 |
| 54 | 14.6 | 14.7 | -0.1 | 0.05 | 0.05 | -0.00 |
| 55 | 287.9 | 287.9 | -0.1 | 0.32 | 0.32 | -0.00 |
| 56 | 82.3 | 82.4 | -0.1 | 0.37 | 0.37 | -0.00 |
| 57 | 11.9 | 12.0 | -0.1 | 0.05 | 0.05 | -0.00 |
| 58 | 4.6 | 4.7 | -0.1 | 0.02 | 0.02 | -0.00 |
| 59 | 4.0 | 4.1 | -0.1 | 0.02 | 0.02 | -0.00 |
| 60 | 0.9 | 0.9 | 0.0 | 1.94 | 1.93 | 0.01 |
| 61 | 0.9 | 0.9 | 0.0 | 1.94 | 1.93 | 0.01 |
| 62 | 0.2 | 0.2 | 0.0 | 0.37 | 0.37 | 0.00 |
| 63 | 0.2 | 0.2 | 0.0 | 0.41 | 0.37 | 0.04 |
| 64 | 0.0 | 0.0 | 0.0 | 0.00 | 0.00 | 0.00 |
| 65 | 0.0 | 0.0 | 0.0 | 0.49 | 0.00 | 0.49 |
| 66 | 0.0 | 0.0 | 0.0 | 0.49 | 0.49 | 0.00 |
| 70 | 278.5 | 276.4 | 2.1 | 112.89 | 112.04 | 0.85 |
| 71 | 278.5 | 276.4 | 2.1 | 112.89 | 112.04 | 0.85 |
| 72 | 278.5 | 276.4 | 2.1 | 98.39 | 97.65 | 0.74 |
| 73 | 261.4 | 259.3 | 2.0 | 92.35 | 91.63 | 0.72 |
| 74 | 186.2 | 184.3 | 1.9 | 65.80 | 65.13 | 0.67 |
| 75 | 165.0 | 163.1 | 1.8 | 58.28 | 57.64 | 0.64 |
| 76 | 278.5 | 276.4 | 2.1 | 14.50 | 14.39 | 0.11 |
| 77 | 122.8 | 121.0 | 1.8 | 6.39 | 6.30 | 0.09 |
| 78 | 159.3 | 157.5 | 1.8 | 64.60 | 63.86 | 0.74 |
| 79 | 162.7 | 158.9 | 3.8 | 65.94 | 64.41 | 1.53 |
The electric machines (generators and motors) are modeled as separate components in the power connection network.
| Component | E_F in MW | E_P in MW | E_D in MW | ε in % | y_Dk in % | y*_Dk in % |
|---|---|---|---|---|---|---|
| Condenser | 3.07 | 1.56 | 1.51 | 50.9 | 3.2 | 9.8 |
| Condenser pump | 0.07 | 0.05 | 0.02 | 71.6 | 0.0 | 0.1 |
| Cooling tower | 1.58 | nan | 1.58 | nan | 3.3 | 10.3 |
| Cooling tower fan | 0.82 | 0.49 | 0.33 | 60.0 | 0.7 | 2.1 |
| Cooling water pump | 0.05 | 0.04 | 0.02 | 70.5 | 0.0 | 0.1 |
| Drum | 74.03 | 74.03 | 0.00 | 100.0 | 0.0 | 0.0 |
| Economizer | 7.52 | 6.99 | 0.52 | 93.0 | 1.1 | 3.4 |
| Evaporator | 26.55 | 25.08 | 1.47 | 94.5 | 3.1 | 9.6 |
| Feedwater pump | 0.72 | 0.58 | 0.15 | 79.9 | 0.3 | 0.9 |
| Feedwater tank | 2.01 | 1.75 | 0.26 | 87.0 | 0.5 | 1.7 |
| HP turbine 1 | 8.57 | 7.70 | 0.87 | 89.9 | 1.8 | 5.6 |
| HP turbine 2 | 3.90 | 3.50 | 0.39 | 89.9 | 0.8 | 2.6 |
| HTF pump | 1.70 | 1.34 | 0.36 | 79.0 | 0.7 | 2.3 |
| High pressure preheater 1 | 1.80 | 1.65 | 0.15 | 91.6 | 0.3 | 1.0 |
| High pressure preheater 1 subcooling | 0.23 | 0.21 | 0.02 | 91.9 | 0.0 | 0.1 |
| High pressure preheater 2 | 2.22 | 2.08 | 0.14 | 93.5 | 0.3 | 0.9 |
| High pressure preheater 2 subcooling | 0.15 | 0.14 | 0.01 | 93.1 | 0.0 | 0.1 |
| LP turbine 1 | 6.36 | 5.85 | 0.51 | 92.0 | 1.1 | 3.3 |
| LP turbine 2 | 7.16 | 6.74 | 0.42 | 94.2 | 0.9 | 2.7 |
| LP turbine 3 | 5.39 | 5.10 | 0.28 | 94.7 | 0.6 | 1.8 |
| LP turbine 4 | 5.03 | 4.50 | 0.54 | 89.4 | 1.1 | 3.5 |
| LP turbine 5 | 4.57 | 3.00 | 1.57 | 65.7 | 3.3 | 10.2 |
| Low pressure preheater 1 | 0.33 | 0.22 | 0.11 | 66.3 | 0.2 | 0.7 |
| Low pressure preheater 1 subcooling | 0.03 | 0.02 | 0.02 | 54.0 | 0.0 | 0.1 |
| Low pressure preheater 2 | 0.71 | 0.55 | 0.16 | 77.9 | 0.3 | 1.0 |
| Low pressure preheater 2 subcooling | 0.06 | 0.04 | 0.02 | 69.4 | 0.0 | 0.1 |
| Low pressure preheater 3 | 1.04 | 0.88 | 0.16 | 84.5 | 0.3 | 1.1 |
| Low pressure preheater 3 subcooling | 0.05 | 0.04 | 0.01 | 80.1 | 0.0 | 0.1 |
| Merge 1 | -0.00 | 0.00 | -0.00 | -0.0 | -0.0 | -0.0 |
| Merge 2 | 0.00 | 0.00 | 0.00 | 0.0 | 0.0 | 0.0 |
| Merge 3 | 0.00 | 0.00 | 0.00 | 0.0 | 0.0 | 0.0 |
| Merge 4 | -0.00 | 0.00 | -0.00 | -0.0 | -0.0 | -0.0 |
| Merge 5 | 1.98 | 1.90 | 0.08 | 95.9 | 0.2 | 0.5 |
| Parabolic trough | 47.63 | 46.95 | 0.68 | 98.6 | 1.4 | 4.4 |
| Reheater | 8.11 | 6.88 | 1.23 | 84.9 | 2.6 | 8.0 |
| Splitter 1 | nan | nan | 0.00 | nan | 0.0 | 0.0 |
| Splitter 2 | nan | nan | 0.00 | nan | 0.0 | 0.0 |
| Splitter 3 | nan | nan | -0.00 | nan | -0.0 | -0.0 |
| Splitter 4 | nan | nan | -0.00 | nan | -0.0 | -0.0 |
| Splitter 5 | nan | nan | 0.00 | nan | 0.0 | 0.0 |
| Splitter 6 | nan | nan | 0.00 | nan | 0.0 | 0.0 |
| Splitter 7 | nan | nan | 0.00 | nan | 0.0 | 0.0 |
| Superheater | 6.05 | 5.53 | 0.52 | 91.4 | 1.1 | 3.4 |
| Valve 1 | 0.00 | nan | 0.00 | nan | 0.0 | 0.0 |
| Valve 2 | 0.01 | nan | 0.01 | nan | 0.0 | 0.0 |
| Valve 3 | 0.00 | nan | 0.00 | nan | 0.0 | 0.0 |
| Valve 4 | 0.00 | nan | 0.00 | nan | 0.0 | 0.0 |
| Valve 5 | 0.00 | nan | 0.00 | nan | 0.0 | 0.0 |
| gen hpt1 | 7.70 | 7.47 | 0.23 | 97.0 | 0.5 | 1.5 |
| gen hpt2 | 3.50 | 3.40 | 0.11 | 97.0 | 0.2 | 0.7 |
| gen lpt1 | 5.85 | 5.68 | 0.18 | 97.0 | 0.4 | 1.1 |
| gen lpt2 | 6.74 | 6.54 | 0.20 | 97.0 | 0.4 | 1.3 |
| gen lpt3 | 5.10 | 4.95 | 0.15 | 97.0 | 0.3 | 1.0 |
| gen lpt4 | 4.50 | 4.36 | 0.13 | 97.0 | 0.3 | 0.9 |
| gen lpt5 | 3.00 | 2.91 | 0.09 | 97.0 | 0.2 | 0.6 |
| mot condpump | 0.07 | 0.07 | 0.00 | 95.0 | 0.0 | 0.0 |
| mot cwp | 0.06 | 0.05 | 0.00 | 95.0 | 0.0 | 0.0 |
| mot fan | 0.87 | 0.82 | 0.04 | 95.0 | 0.1 | 0.3 |
| mot fwp | 0.76 | 0.72 | 0.04 | 95.0 | 0.1 | 0.2 |
| mot ptpump | 1.79 | 1.70 | 0.09 | 95.0 | 0.2 | 0.6 |
| E_F in MW | E_P in MW | E_D in MW | E_L in MW | ε in % | |
|---|---|---|---|---|---|
| 0 | 47.63 | 31.77 | 15.37 | 0.49 | 66.7 |
The state of this repository is archived via zenodo. If you are using the TESPy model within your own research, you can refer to this model via the zenodo doi: 10.5281/zenodo.4726800.
MIT License
Copyright (c) Francesco Witte, Julius Meier, Ilja Tuschy, Mathias Hofmann
Permission is hereby granted, free of charge, to any person obtaining a copy of this software and associated documentation files (the "Software"), to deal in the Software without restriction, including without limitation the rights to use, copy, modify, merge, publish, distribute, sublicense, and/or sell copies of the Software, and to permit persons to whom the Software is furnished to do so, subject to the following conditions:
The above copyright notice and this permission notice shall be included in all copies or substantial portions of the Software.
THE SOFTWARE IS PROVIDED "AS IS", WITHOUT WARRANTY OF ANY KIND, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE AND NONINFRINGEMENT. IN NO EVENT SHALL THE AUTHORS OR COPYRIGHT HOLDERS BE LIABLE FOR ANY CLAIM, DAMAGES OR OTHER LIABILITY, WHETHER IN AN ACTION OF CONTRACT, TORT OR OTHERWISE, ARISING FROM, OUT OF OR IN CONNECTION WITH THE SOFTWARE OR THE USE OR OTHER DEALINGS IN THE SOFTWARE.