Program Version,EnergyPlus, Version 24.1.0-9d7789a3ac, YMD=2026.06.06 18:45,
   ************* Beginning Zone Sizing Calculations
   ** Warning ** Site:GroundTemperature:BuildingSurface: Some values fall outside the range of 15-25C.
   **   ~~~   ** These values may be inappropriate.  Please consult the Input Output Reference for more details.
   ** Warning ** ProcessScheduleInput: Schedule:Compact="HEATING_SCHEDULE" has missing day types in Through=12/31
   **   ~~~   ** Last "For" field=FOR:SUMMERDESIGNDAY
   **   ~~~   ** Missing day types="Holiday","CustomDay1","CustomDay2"
   **   ~~~   ** Missing day types will have 0.0 as Schedule Values
   ** Warning ** ProcessScheduleInput: Schedule:Compact="CONTROL_TYPE_SCHEDULE" has missing day types in Through=12/31
   **   ~~~   ** Last "For" field=FOR:SUMMERDESIGNDAY
   **   ~~~   ** Missing day types="Holiday","CustomDay1","CustomDay2"
   **   ~~~   ** Missing day types will have 0.0 as Schedule Values
   ** Warning ** GetSurfaceData: Construction WALL_OSB of interzone surface RDC_WALL3 does not have the same materials in the reverse order as the construction WALL_OSB of adjacent surface MEETING..FACE1
   **   ~~~   ** or the properties of the reversed layers are not correct due to differing layer front and back side values
   **   ~~~   ** ...but Nominal U values are similar, diff=[0.0000] ... simulation proceeds.
   **   ~~~   ** ...if the two zones are expected to have significantly different temperatures, the proper "reverse" construction should be created.
   **   ~~~   ** ...this problem for this pair will not be reported again.
   ** Warning ** CalcSurfaceCentroid: 2 Surfaces have the Z coordinate < 0.
   **   ~~~   ** ...in any calculations, Wind Speed will be 0.0 for these surfaces.
   **   ~~~   ** ...in any calculations, Outside temperatures will be the outside temperature + 9.750E-003 for these surfaces.
   **   ~~~   ** ...that is, these surfaces will have conditions as though at ground level.
   ** Warning ** CheckUsedConstructions: There are 12 nominally unused constructions in input.
   **   ~~~   ** For explicit details on each unused construction, use Output:Diagnostics,DisplayExtraWarnings;
   ** Warning ** DetermineShadowingCombinations: There are 1 surfaces which are receiving surfaces and are non-convex.
   **   ~~~   ** ...Shadowing values may be inaccurate. Check .shd report file for more surface shading details
   **   ~~~   ** ...Add Output:Diagnostics,DisplayExtraWarnings; to see individual warnings for each surface.
   ** Severe  ** GetHWBaseboardInput:ZoneHVAC:Baseboard:RadiantConvective:Water="RDC BASEBOARD", the number of surface/radiant fraction groups entered was less than the allowable minimum.
   **   ~~~   ** ...the minimum that must be entered=[1].
   ** Warning ** GetHWBaseboardInput:ZoneHVAC:Baseboard:RadiantConvective:Water="RDC BASEBOARD", Summed radiant fractions for people + surface groups < 1.0
   **   ~~~   ** The rest of the radiant energy delivered by the baseboard heater will be lost
   ** Severe  ** GetHWBaseboardInput:ZoneHVAC:Baseboard:RadiantConvective:Water="RPLUS1 BASEBOARD", the number of surface/radiant fraction groups entered was less than the allowable minimum.
   **   ~~~   ** ...the minimum that must be entered=[1].
   ** Warning ** GetHWBaseboardInput:ZoneHVAC:Baseboard:RadiantConvective:Water="RPLUS1 BASEBOARD", Summed radiant fractions for people + surface groups < 1.0
   **   ~~~   ** The rest of the radiant energy delivered by the baseboard heater will be lost
   **  Fatal  ** GetHWBaseboardInput:ZoneHVAC:Baseboard:RadiantConvective:WaterErrors found getting input. Program terminates.
   ...Summary of Errors that led to program termination:
   ..... Reference severe error count=2
   ..... Last severe error=GetHWBaseboardInput:ZoneHVAC:Baseboard:RadiantConvective:Water="RPLUS1 BASEBOARD", the number of surface/radiant fraction groups entered was less than the allowable minimum.
   ************* Warning:  Node connection errors not checked - most system input has not been read (see previous warning).
   ************* Fatal error -- final processing.  Program exited before simulations began.  See previous error messages.
   *************
   ************* ===== Final Error Summary =====
   ************* The following error categories occurred.  Consider correcting or noting.
   ************* Nominally Unused Constructions
   ************* ..The nominally unused constructions warning is provided to alert you to potential conditions that can cause
   ************* ..extra time during simulation. Each construction is calculated by the algorithm indicated in the HeatBalanceAlgorithm
   ************* ..object. You may remove the constructions indicated (when you use the DisplayExtraWarnings option).
   *************
   ************* EnergyPlus Warmup Error Summary. During Warmup: 0 Warning; 0 Severe Errors.
   ************* EnergyPlus Sizing Error Summary. During Sizing: 8 Warning; 2 Severe Errors.
   ************* EnergyPlus Terminated--Fatal Error Detected. 9 Warning; 2 Severe Errors; Elapsed Time=00hr 00min  0.75sec

Activity

Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment

Metadata

Metadata

Assignees

No one assigned

    Labels

    No labels
    No labels

    Type

    No type

    Projects

    No projects

      Milestone

      No milestone

      Relationships

      None yet

      Development

      No branches or pull requests

      Issue actions