apcupsd

This plugin is to be used to track UPS status from the apcupsd daemon, from the Network UPS Tools (NUT) upsd server, as well as from SNMP enabled UPS'. The apcupsd daemon is able to provide information on APC and other types of UPS' over various network typologies such as USB, Modbus, Ethernet, etc. NUT provides the same for a very wide range of UPS vendors. I have added basic SNMP support in order to provide direct access to certain models over the SNMP protocol thus removing the need for an apcupsd host to provide the monitoring details as well.

Each apcupsd UPS is defined by a network address and port name. Cacti uses the apcaccess command to gather statistics from the UPS and store them in the Cacti database for apcupsd enabled UPS'. The data stored in the Cacti database can be used for Reporting, Graphing, and Alerting.

Purpose

This plugin allows Cacti Administrators to easily track their Data Center UPS's that do not support SNMP protocol, but that are supported by the APCUPSD daemon or by NUT.

Features

  • Track UPS status'

  • Log information to Cacti database

  • Three collector types: apcupsd (via apcaccess), SNMP, and NUT (via the native NUT network protocol)

  • Fleet and per-UPS dashboards, with sortable tables

Cacti compatibility

If you are running a version of Cacti below 1.2.31, please add the function below to the applySkin() function in include/layout.js to enable the Cancel buttons on forms to work:

$(document).off('click.cactiReturnTo', '.cactiReturnTo')
    .on('click.cactiReturnTo', '.cactiReturnTo', function(event) {
        event.preventDefault();
        cactiReturnTo($(this).attr('data-url'));
    });

Installation

Install just like any other plugin, just throw it in the plugin directory, and Install and Enabled from the Plugin Management Interface. To monitor apcupsd UPS', your Cacti install will require the Linux apcupsd package be installed and apcaccess be in the system path. NUT UPS' need no extra software on the Cacti poller.

After you have installed the plugin, install the Device Package in the templates folder from Console > Import/Export > Import Package. This Device Template will be used for showing available graphs.

The dashboards read each reading's min, average and max from the RRD files of the UPS's Cacti Device, so the device needs its graphs. They are created when the device is first added, but if a device has none (for example the Device Package was imported afterwards), tick the UPS on the UPSes page and choose Run Graph Automation from the action dropdown. It runs Cacti's graph automation for the linked device, the same as Apply Automation Rules on the Devices page, and leaves graphs that already exist alone. It needs the Sites/Devices/Data permission.

Monitoring UPS' with NUT

Support for Network UPS Tools (NUT) is new in version 1.4.0. The plugin talks to the NUT upsd data server directly with a native PHP implementation of the NUT network protocol, so the NUT client tools (upsc) do not have to be installed on the Cacti poller, and curl is not involved. The only requirement is that the poller can open a TCP connection to upsd, which listens on port 3493 by default.

To add a NUT UPS, go to the UPSes page, add a UPS, and choose the NUT Based type:

  • Hostname and TCP Port: the host running upsd and its port (3493).

  • NUT UPS Name: the name of the UPS on that server, as listed by upsc -l <host> (the ups in ups@host). One upsd can serve several UPS', so add one UPS here for each of them.

  • NUT Username and NUT Password: optional. NUT servers have always allowed anonymous read-only access and that is how they are normally monitored, so leave these blank unless your upsd.users is set up to require authentication. A user with no actions is enough, as the plugin only reads data. The password is stored in the Cacti database the same way SNMP community strings and passwords are.

  • Use TLS (STARTTLS): encrypts the connection before any credentials are sent (the openssl PHP extension is required). The server certificate and host name are verified, so by default the certificate must be trusted by the Cacti poller. For a homelab with a self-signed certificate there are two ways around that:

    • CA / Certificate File (recommended): the full path, on the poller, to a PEM file holding the CA certificate, or the self-signed server certificate itself (for example /etc/nut/upsd.pem copied from the NUT server). The server is still authenticated against that file, and the Hostname must match a name in the certificate.

    • Allow Self-Signed Certificate: accepts any certificate without checking it. The connection is encrypted but the server's identity is not verified, so a man-in-the-middle could still read the NUT credentials. Use it only on a network you trust, and prefer the certificate file.

  • Timeout (seconds): how long the poller waits for the NUT server, from 1 to 120 seconds (5 by default). It bounds the connection attempt and each reply, and the connection plus the whole conversation together never take longer than twice the timeout, so an unresponsive server cannot hold up the poller. The same setting applies to apcupsd UPS', where apcaccess is stopped if it has not finished in time. SNMP UPS' keep using the SNMP timeout.

On the NUT server, upsd only listens on localhost by default. To let a Cacti poller reach it, add a LISTEN line to upsd.conf (for example LISTEN 0.0.0.0 3493), restart upsd, and allow the poller through the firewall.

NUT reports power state with short flags. These are translated into the apcupsd vocabulary when the data is saved (OL becomes ONLINE, OB becomes ONBATT, LB becomes LOWBATT, RB becomes REPLACEBATT, and OVER becomes OVERLOAD), so the dashboards and fleet totals treat NUT and apcupsd UPS' the same way. A Cacti device is created for each NUT UPS automatically, the same as for apcupsd UPS'.

Possible Bugs

If you figure out this problem, see the Cacti forums!

Future Changes

Currently the SNMP based collection is functional but only covering APC UPS'.
I will likely fix that in the next release. Need some help from others.

Measured real power (ups.realpower) is reported by many NUT UPS' but is not stored yet; the plugin continues to estimate watts from the nominal power rating and the load.

Got any ideas or complaints, please log an issue on GitHub.